Thin helper to validate lightsim2grid against PowSyBl Open Load Flow (OLF) on
identical inputs.
The workflow:
1. Solve the network with OLF *with* outer loops.
2. :func:`bake_outer_loops` to freeze the converged outer-loop state into the
network (see ``_olf_bake``).
3. Optionally apply the same topology change (e.g. a line outage) to both
engines.
4. Solve the baked network loop-free in OLF (see :func:`remove_outer_loops`,
applied to the same ``olf_loop_params`` used for step 1) and in
lightsim2grid.
5. Compare bus voltage magnitude (pu) and angle (deg).
Bus mapping
-----------
lightsim2grid uses its own internal solver-bus indexing, not the IIDM bus
order. The mapping is taken directly from ``grid._ls_to_orig``: solver bus
``i`` corresponds to pypowsybl original bus index ``_ls_to_orig[i]``, i.e.
``network.get_buses().index[_ls_to_orig[i]]``. Building the grid with
``sort_index=False`` makes ``_ls_to_orig`` the identity, so it aligns 1:1 with
``get_buses()``; ``buses_for_sub=False`` keeps the bus set simple. This covers
*every* solver bus, including injection-free junction buses, which a mapping
inferred from element names cannot.
"""
from dataclasses import dataclass
import numpy as np
import pandas as pd
import pypowsybl as pp
import pypowsybl.loadflow as lf
from .initLSGrid import init as init_from_pypowsybl
from ._olf_bake import bake_outer_loops
from ._olf_params import remove_outer_loops
def iidm_bus_voltages(network) -> pd.DataFrame:
"""Per-bus |V| (pu) and angle (deg) from a solved IIDM network, indexed by
bus id (in ``get_buses()`` order), with the kV->pu conversion applied."""
buses = network.get_buses()
vls = network.get_voltage_levels()[["nominal_v"]]
buses = buses.join(vls, on="voltage_level_id")
out = pd.DataFrame(index=buses.index)
out["vm_pu"] = buses["v_mag"] / buses["nominal_v"]
out["va_deg"] = buses["v_angle"]
return out
def lightsim_bus_to_iidm(grid, network) -> dict:
"""Map lightsim2grid solver bus index -> IIDM bus id.
Uses lightsim2grid's own ``_ls_to_orig`` array, which gives the index of
each solver bus in pypowsybl's *original* bus order. Paired with
``network.get_buses().index`` (same original order) this pins every solver
bus -- including injection-free junction buses -- to a concrete IIDM bus
id, with no element-name parsing and no guessing.
Requires the grid to have been built with ``init_from_pypowsybl(...,
sort_index=False, buses_for_sub=False)`` so that the original order matches
``get_buses()`` one-to-one.
"""
ls_to_orig = np.asarray(grid._ls_to_orig)
orig_bus_ids = list(network.get_buses().index)
return {
ls: orig_bus_ids[orig]
for ls, orig in enumerate(ls_to_orig)
if orig < len(orig_bus_ids)
}
[docs]
@dataclass
class ComparisonResult:
"""Outcome of :func:`compare_baked`: how far lightsim2grid and OLF disagree.
Attributes
----------
max_dvm_pu : float
Largest absolute voltage-magnitude difference, in per unit, over every
bus common to both engines.
max_dva_deg : float
Largest absolute voltage-angle difference, in degrees (raw).
max_dva_deg_offset_removed : float
Same as ``max_dva_deg`` but with a uniform angle offset removed first.
A constant offset on all buses is just a difference of reference-datum
convention between the two engines, not a physical disagreement, so this
is usually the meaningful angle metric.
table : pandas.DataFrame
Per-bus detail, indexed by IIDM bus id, with the OLF and lightsim2grid
magnitudes / angles and their differences (columns ``olf_vm``,
``ls_vm``, ``olf_va``, ``ls_va``, ``dvm``, ``dva``).
"""
max_dvm_pu: float
max_dva_deg: float
max_dva_deg_offset_removed: float
table: pd.DataFrame
def __repr__(self):
return (
f"ComparisonResult(max |dV| = {self.max_dvm_pu:.3e} pu, "
f"max |dAngle| = {self.max_dva_deg:.3e} deg, "
f"offset-removed = {self.max_dva_deg_offset_removed:.3e} deg)"
)
[docs]
def compare_baked(
network_factory,
slack_gen_id: str,
line_outages=None,
trafo_outages=None,
olf_loop_params: "lf.Parameters | None" = None,
):
"""Bake, optionally apply outages, solve in both engines, and compare.
Parameters
----------
network_factory : callable
Returns a fresh pypowsybl Network. Called twice (once per engine) so the two starts are identical.
lightsim2grid mutates/consumes the network it is built from, so a fresh
instance is needed for each side.
slack_gen_id : str
Generator id to use as the lightsim2grid slack.
line_outages, trafo_outages : list of str, optional
IIDM ids to disconnect identically in both engines after baking.
olf_loop_params : pypowsybl.loadflow.Parameters, optional
Parameters for the initial *with-loops* OLF solve. Defaults to
distributed slack + reactive limits.
Returns
-------
ComparisonResult
"""
line_outages = line_outages or []
trafo_outages = trafo_outages or []
if olf_loop_params is None:
# ``twt_split_shunt_admittance=True`` matches the transformer model used
# by the loop-free OLF solve and by lightsim2grid, so the baked
# setpoints are derived under the same model as the comparison solve.
olf_loop_params = lf.Parameters(
distributed_slack=True,
use_reactive_limits=True,
balance_type=pp.loadflow.BalanceType.PROPORTIONAL_TO_GENERATION_P_MAX,
twt_split_shunt_admittance=True,
)
# Derived from ``olf_loop_params`` (not built independently): this guarantees
# every field the with-loops and loop-free solves do not differ on by design
# (twt_split_shunt_admittance, component_mode, voltage_init_mode, ...) is
# actually identical between them, so the comparison isolates the outer-loop
# effect that baking neutralizes rather than an unrelated model difference.
loop_free_params = remove_outer_loops(olf_loop_params)
# ---- OLF side: with-loops solve, bake, outage, loop-free solve ----
n_olf = network_factory()
lf.run_ac(n_olf, olf_loop_params)
bake_outer_loops(n_olf)
for lid in line_outages:
n_olf.update_lines(id=lid, connected1=False, connected2=False)
for tid in trafo_outages:
n_olf.update_2_windings_transformers(id=tid, connected1=False, connected2=False)
res = lf.run_ac(n_olf, loop_free_params)
if res[0].status != pp.loadflow.ComponentStatus.CONVERGED:
raise RuntimeError(f"OLF loop-free did not converge: {res[0].status}")
olf_v = iidm_bus_voltages(n_olf) # indexed by IIDM bus id
# ---- lightsim2grid side: bake, outage, solve ----
n_ls = network_factory()
lf.run_ac(n_ls, olf_loop_params)
bake_outer_loops(n_ls)
grid = init_from_pypowsybl(
n_ls,
gen_slack_id=slack_gen_id,
sort_index=False,
buses_for_sub=False,
)
solver_to_iidm = lightsim_bus_to_iidm(grid, n_ls)
line_ids = list(n_ls.get_lines().index)
for lid in line_outages:
grid.deactivate_powerline(line_ids.index(lid))
trafo_ids = list(n_ls.get_2_windings_transformers().index)
for tid in trafo_outages:
grid.deactivate_trafo(trafo_ids.index(tid))
V = grid.ac_pf(np.full(grid.total_bus(), 1.06 + 0j), 20, 1e-10)
if len(V) == 0:
raise RuntimeError("lightsim2grid did not converge")
n_bus = len(V)
ls_v = pd.DataFrame(
{
"vm_pu": [abs(V[s]) for s in range(n_bus)],
"va_deg": [np.degrees(np.angle(V[s])) for s in range(n_bus)],
},
index=[solver_to_iidm.get(s) for s in range(n_bus)],
)
ls_v = ls_v[ls_v.index.notna()] # drop any unmapped junction bus
# ---- compare on the intersection of mapped IIDM bus ids ----
common = olf_v.index.intersection(ls_v.index)
table = pd.DataFrame(
{
"olf_vm": olf_v.loc[common, "vm_pu"],
"ls_vm": ls_v.loc[common, "vm_pu"],
"olf_va": olf_v.loc[common, "va_deg"],
"ls_va": ls_v.loc[common, "va_deg"],
}
)
table["dvm"] = (table["olf_vm"] - table["ls_vm"]).abs()
table["dva"] = (table["olf_va"] - table["ls_va"]).abs()
# A uniform angle offset is just a reference-datum convention difference;
# report both raw and offset-removed.
offset = (table["olf_va"] - table["ls_va"]).median()
dva_rel = ((table["olf_va"] - table["ls_va"]) - offset).abs()
return ComparisonResult(
max_dvm_pu=float(table["dvm"].max()),
max_dva_deg=float(table["dva"].max()),
max_dva_deg_offset_removed=float(dva_rel.max()),
table=table,
)