Bake PowSyBl Open Load Flow (OLF) outer-loop results into an IIDM network so
that a subsequent *outer-loop-free* power flow -- in OLF itself or in
lightsim2grid -- reproduces the converged state exactly.
Why this exists
---------------
lightsim2grid solves a single power-flow problem: it does not run the discrete
"outer loops" that OLF runs (distributed slack, reactive-limit PV<->PQ
switching, transformer/shunt voltage control, phase control, ...). Those loops
change the input of the inner solves (*eg* the input of the inner Newton
Raphson) between iterations: a generator that hits its Q limit becomes a
fixed-Q (PQ) injection, a tap changer settles on a discrete position, the
slack mismatch is spread over participating units, etc.
If you take the raw network, run OLF *with* outer loops, and then hand the same
raw network to lightsim2grid, the two engines disagree -- not because the
solvers differ, but because they are solving different problems.
``bake_outer_loops`` rewrites the network's input setpoints to the values the
outer loops settled on, and disables the corresponding regulation, so the
problem becomes a plain power flow. After baking, OLF (loop-free) and
lightsim2grid *should* agree to solver tolerance, and keep agreeing through
topology changes (line/transformer outages) applied identically to both --
this does not always hold in practice (see e.g. multi-root / basin-boundary
cases where the two engines land on different, both-valid, roots).
The loop-free OLF parameters that reproduce the baked operating point are
available as :func:`lightsim2grid.network.get_pypowsybl_loopfree_parameters`.
What gets baked
---------------
* Discrete tap / section positions (ratio tap, phase tap, shunt section):
the solved position (``solved_tap_position`` / ``solved_section_count``) is
copied into the input position and regulation is switched off. The copy is
guarded: it only happens where the changer was regulating AND a solved value
exists, because ``solved_tap_position`` is NaN for changers that did not take
part in an outer loop -- copying NaN would destroy the input tap.
* Generators dispatched at (approximately) 0 MW with a strictly positive
``min_p``: OLF never sets these up as voltage-controlling PV buses in the
first place (``generatorsWithZeroMwTargetAreNotStarted``, "not started"),
regardless of their ``voltage_regulator_on``/``target_v`` attributes. Frozen
to fixed-Q (their realized reactive output) before the reactive-limit switch
below runs. A generator with ``min_p <= 0`` (legitimately allowed to sit at
0 MW) is left alone.
* PV -> PQ reactive-limit switches (generators, VSC converter stations): only
the units whose realized reactive power actually sits at a Q limit are frozen
to fixed-Q at that limit, with voltage regulation switched off. The limit, not
the reported ``q``, when the two are within 1e-3 MVAr: OLF can report a different
split of a bus' reactive power among its units than the one it injected; a unit
further from its limit injects what it reports (see :func:`_baked_q_at_limit`). Units still
inside their limits keep voltage control -- their equation type is unchanged.
Units with NaN (unlimited) reactive limits are never frozen, since NaN
comparisons are False.
* For generators, every one of the voltage-control rules above and below is
subordinate to what the reference solve shows OLF actually did: a generator
whose regulated bus sits exactly at its ``target_v`` (to 1e-8 pu, see
``_TARGET_V_HELD_TOL_PU``; OLF pins a PV magnitude to machine precision) was
voltage-controlled and is never frozen, whatever the rules say; a regulating
generator whose target was NOT held was not controlling (switched, not
started, discarded, merged, below OLF's ``generatorVoltageControlMinNominalVoltage``,
...) and is frozen to its realized Q in a final catch-all pass
(:func:`_bake_generator_voltage_control_not_held`). On real grid snapshots
this catch-all is what decides the bulk of the disagreements: it un-freezes
the generators the rules alone froze although OLF held their target (mostly a
target-voltage check that used the generator's own terminal nominal voltage
instead of the regulated bus's) and freezes the ones they left regulating
although OLF did not. One opt-in exception:
``bake_saturated_voltage_control=True`` also freezes a held unit whose Q sits
at a limit (to ``_Q_SATURATED_HELD_TOL_MVAR``, not to the relative tolerance: a
held unit with headroom left is still regulating, as is one whose bus still has a
regulating unit with headroom: OLF switches buses, not units), at that limit.
* Generators OLF's own voltage-control consistency checks would discard for a
reason other than "not started": too small a reactive range (default
``reactiveRangeCheckMode``, widest ``max_q - min_q`` below 1 MVar) or an
implausible ``target_v`` (outside 0.8-1.2 pu of nominal, on buses above 20 kV).
Frozen to fixed-Q the same way as the "not started" case above, since OLF
itself never actually voltage-controlled them either.
* A remotely-regulating generator whose own bus already hosts another
connected, locally-regulating generator: the shared bus's voltage is already
pinned by the local unit, so the remote unit's reactive injection cannot
independently move any voltage (including the one it targets). Frozen to
fixed-Q the same way, mirroring OLF's own handling of this configuration
(see :func:`_bake_remote_control_bus_conflicts`).
* The reactive target of a non-regulating generator, where the reference solve injected
something else: OLF's default ``forceTargetQInReactiveLimits`` clamps it into the
reactive capability at the generator's active power, a clamp the loop-free parameters
(reactive limits off) and lightsim2grid do not apply. The realized value is written
into ``target_q`` (see :func:`_bake_generator_target_q_forced_in_limits`).
* Active-power redistribution from distributed slack / area interchange: the
realized P is written back into the target P of generators and batteries
(and optionally loads, if the slack was distributed on load). A unit whose
realized P comes back a round-off outside its active target range (a unit
dispatched at ``max_p``) is put back on that bound, so that OLF does not drop it
from the slack of the baked network (see :func:`_snap_realized_into_target_range`).
* Generators OLF's own ``checkActivePowerControl`` would exclude from
slack-distribution participation (dispatched at ~0 MW, an implausible
``max_p``, ``target_p`` outside ``[min_p, max_p]``, or a degenerate P range):
their ``activePowerControl`` extension's ``participate`` flag is set to
``False`` (created if absent), so neither a subsequent pypowsybl OLF re-solve
nor lightsim2grid's own distributed slack -- which reads that same flag --
puts slack mismatch back onto them. So are the generators OLF *capped* while
distributing the reference mismatch (realized dispatch at ``max_p`` for a
positive mismatch, at ``min_p`` for a negative one): they took no share, and
a static distribution that gives them one is wrong by exactly that share.
* Static var compensators whose realized reactive output sits at (or beyond)
their voltage-dependent susceptance envelope (``Q(V) = b * V^2``, ``b`` in
``b_min``..``b_max``, shifted by the ``b0`` of its standby automaton when it carries
one, recomputed in MVAr at the SVC's own solved terminal
voltage) are frozen to fixed-Q (``REACTIVE_POWER`` mode), with the generator
rule: the tolerance only proposes a candidate, and an SVC whose regulated bus
the reference solve held at its target was regulating and is left so, unless
it sits exactly at its limit while another controller of that bus is still
inside its range, or ``bake_saturated_voltage_control`` is set and it sits at
its limit to ``_Q_SATURATED_HELD_TOL_MVAR``. An SVC inside
its envelope is left regulating (its target reproduces the OLF result
exactly, since it isn't saturated).
* Angle-droop ("AC emulation") hvdc lines OLF's ``AcHvdcAcEmulationLimits`` outer
loop saturated: the sending converter's realized active power sits at the line's
limit in that direction (``hvdcOperatorActivePowerRange`` when present, ``max_p``
otherwise). The droop is switched off and the line becomes a fixed setpoint at
that limit, in that direction (see :func:`_bake_hvdc_ac_emulation_limits`). A
line still in its linear regime keeps its droop.
* Voltage-regulating static var compensators carrying a "standby automaton"
(``standby=True``; OLF ignores the extension on any other SVC): OLF's own
outer loop starts these as a fixed ``b0`` shunt (no voltage control) and only
switches them to active voltage control once the voltage of the bus they
control crosses a low/high threshold. The static ``regulating`` /
``target_v`` attributes do *not* reflect this -- they read as if the SVC
were always actively regulating. Resolved before the reactive-limit
switch above: an SVC that stayed within its deadband is frozen to fixed-Q
(0 when, as commonly configured, ``b0 == 0``), and returned by
``bake_outer_loops`` so that lightsim2grid can report a later switch; one
that crossed a threshold is switched to ``VOLTAGE`` mode targeting the
corresponding ``low_voltage_setpoint`` / ``high_voltage_setpoint`` (then
still eligible for the ordinary saturation freeze).
Verified against pypowsybl 1.15.0. The OLF-internal round trip (solve with
outer loops -> bake -> solve loop-free) reproduces bus voltages to ~2e-4 kV /
~1e-5 deg, both on IEEE-14 (with a forced reactive-limit switch) and on the
four-substations node-breaker network, which carries VSC and LCC HVDC, an SVC
regulating voltage, a shunt, and ratio + phase tap changers.
"""
from typing import NamedTuple
import numpy as np
import pandas as pd
# every OLF-mirrored constant and reading-back tolerance lives in one module, see there
from ._olf_const import (
_MAX_PLAUSIBLE_ACTIVE_POWER_MW,
_MAX_PLAUSIBLE_TARGET_V_PU,
_MIN_NOMINAL_V_FOR_TARGET_V_CHECK_KV,
_MIN_PLAUSIBLE_TARGET_V_PU,
_MIN_REACTIVE_RANGE_MVAR,
_Q_LIMIT_TOL_ABS,
_Q_LIMIT_TOL_REL,
_TARGET_Q_TOL_MVAR,
_TARGET_V_HELD_TOL_PU,
_ZERO_P_TOL,
_HVDC_P_LIMIT_TOL_MW,
_Q_SATURATED_HELD_TOL_MVAR,
)
from ._aux_add_hvdc import _hvdc_pmax_per_direction
from ._aux_add_svc import _svc_standby_b0
def _q_limit_tol(qmin, qmax):
# An unset reactive-limit box defaults to +/-Double.MAX in pypowsybl (an
# "unbounded" sentinel, not a real 3.6e308 MVAr range): subtracting the two
# overflows to +inf, which is exactly the "no limit" case filtered out below --
# expected and already handled, so silence the resulting RuntimeWarning.
with np.errstate(over="ignore"):
rng = np.asarray(qmax) - np.asarray(qmin)
# A relative tolerance on that overflowed/absurd range would swallow every
# generator. Treat absurdly large / non-finite ranges as "no limit" -- no
# relative bonus, just the absolute floor -- rather than let them dominate max().
rng = np.where(np.isfinite(rng) & (rng < 1e6), rng, 0.0)
return np.maximum(_Q_LIMIT_TOL_ABS, _Q_LIMIT_TOL_REL * rng)
def _get_buses(network):
"""The bus frame every step of the bake reads (solved ``v_mag``, ``voltage_level_id``,
``synchronous_component``, plus the ``nominal_v`` of its voltage level).
Fetched once per bake and handed down: baking rewrites input setpoints only, never
the solved state nor the topology, so the frame stays valid from the first step to
the last -- and each fetch is a full round trip to the Java network.
"""
buses = network.get_buses(attributes=["v_mag", "voltage_level_id", "synchronous_component"])
nominal_v = network.get_voltage_levels(attributes=["nominal_v"])["nominal_v"]
buses["nominal_v"] = nominal_v.reindex(buses["voltage_level_id"].to_numpy()).to_numpy(float)
return buses
def _keep_only_main_comp(df_el, df_bus):
"""
keep only element (modeled in df_el) that are on the main component => bus_els["synchronous_component"] == 0
This does not deactivate anything.
"""
comp = df_el["bus_id"].map(df_bus["synchronous_component"])
return df_el[df_el["connected"].to_numpy(bool) & (comp == 0).to_numpy()]
def _reactive_limits(df: pd.DataFrame):
"""Return (qmin, qmax) in *generator* convention.
Prefer the P-dependent capability-curve limits (``min_q_at_p`` /
``max_q_at_p``) when present and finite; fall back to the fixed
``min_q`` / ``max_q`` box otherwise.
"""
if "min_q_at_p" in df.columns:
qmin = df["min_q_at_p"].where(df["min_q_at_p"].notna(), df["min_q"])
qmax = df["max_q_at_p"].where(df["max_q_at_p"].notna(), df["max_q"])
else:
qmin, qmax = df["min_q"], df["max_q"]
return qmin, qmax
def _bound_at_qlimit(df: pd.DataFrame, regulating: pd.Series):
"""Boolean mask of rows that regulate voltage *and* sit at a Q limit,
plus the realized reactive power in generator convention.
``df`` must carry result column ``q`` (load convention) and the reactive
limit columns. ``regulating`` is the per-row voltage-regulation flag.
"""
q_gen = -df["q"] # result column is load convention; flip to generator
qmin, qmax = _reactive_limits(df)
tol = _q_limit_tol(qmin, qmax)
at_max = regulating & (q_gen >= qmax - tol)
at_min = regulating & (q_gen <= qmin + tol)
return (at_max | at_min), q_gen
def _hit_qlimit(df: pd.DataFrame, q_gen: pd.Series):
"""The reactive limit (generator convention, same limits as
:func:`_bound_at_qlimit`) each row's realized output ``q_gen`` sits at: the
nearer of the two, a missing limit counting as infinitely far.
A unit OLF switched at its limit injects exactly that limit, but the ``q`` it
reports is not always it: OLF spreads the reactive target of a bus over the
generators of that bus again when writing the results, so two units of one bus
can each be reported a hair away from what they injected, the bus no longer
balancing. Baking the reported value would then move the injection."""
qmin, qmax = _reactive_limits(df)
to_min = (q_gen - qmin).abs().fillna(np.inf)
to_max = (qmax - q_gen).abs().fillna(np.inf)
return pd.Series(np.where(to_min < to_max, qmin, qmax), index=df.index)
def _baked_q_at_limit(df: pd.DataFrame, q_gen: pd.Series):
"""The fixed reactive output to bake for a unit frozen at its Q limit: the limit
(see :func:`_hit_qlimit`) when the reported ``q`` is within ``_Q_LIMIT_TOL_ABS`` of
it, the reported ``q`` otherwise.
Only a report that close is the misreport of a limit injection: on real grid
snapshots the bus balance is off by exactly the reported discrepancy, which is
what identifies it. The relative tolerance of :func:`_bound_at_qlimit` also
catches units a visible distance from their limit -- settled inside it, or
injecting a ``target_q`` beyond it -- and those do inject what they report
(their bus balances), so the reported value is what must be baked for them."""
limit = _hit_qlimit(df, q_gen)
return limit.where((limit - q_gen).abs() <= _Q_LIMIT_TOL_ABS, q_gen)
[docs]
def bake_outer_loops(
network,
bake_taps: bool = True,
bake_reactive_limits: bool = True,
bake_generator_voltage_control_discards: bool = True,
bake_active_power: bool = True,
bake_active_power_control_participation: bool = True,
bake_remote_voltage_control: bool = False,
balance_on_loads: bool = False,
load_power_factor_constant: bool = False,
keep_only_main_comp: bool=True,
extrapolate_reactive_limits: bool = True,
bake_saturated_voltage_control: bool = False,
bake_hvdc_ac_emulation_limits: bool = True,
return_details: bool = False,
):
"""Rewrite ``network`` input setpoints to the converged outer-loop state.
Call this on a network that has just been solved by OLF *with* outer loops.
Afterwards the network represents a plain power-flow problem: a loop-free
OLF run (see :func:`get_pypowsybl_loopfree_parameters`) or a lightsim2grid
run (via :func:`init_from_pypowsybl`) will reproduce the same operating
point.
Parameters
----------
network
A pypowsybl network, freshly solved with the outer loops enabled.
bake_taps
Copy solved ratio/phase tap positions and shunt sections into the
input positions and disable their regulation.
bake_reactive_limits
Freeze generators / VSC stations that hit a Q limit to fixed-Q (PQ).
bake_generator_voltage_control_discards
Freeze generators OLF's own voltage-control consistency checks would
discard for a reason other than "not started": too small a reactive
range, or an implausible ``target_v`` (see
:func:`_bake_generator_voltage_control_discards`). Also gated by
``bake_reactive_limits`` -- has no effect if that is off.
bake_active_power
Write realized active power back into generator/battery target P
(and load p0/q0 if ``balance_on_loads``).
bake_active_power_control_participation
Zero out (``activePowerControl`` extension ``participate=False``)
slack-distribution participation for generators and batteries OLF's own
``checkActivePowerControl`` would exclude (see
:func:`_bake_active_power_control_participation`). Also gated by
``bake_active_power`` -- has no effect if that is off.
bake_remote_voltage_control
Rewrite remote voltage control to local control at the solved terminal
voltage (see :func:`_bake_remote_voltage_control`). Needed so that
remote-regulating generators can sit on a (distributed) slack bus, which
lightsim2grid v1 does not otherwise support.
balance_on_loads
Set if the slack was distributed on loads (BalanceType
PROPORTIONAL_TO_LOAD / CONFORM_LOAD).
load_power_factor_constant
Mirror OLF's ``loadPowerFactorConstant``: also rewrite load q0 so the
power factor is preserved.
keep_only_main_comp
Only elements of the main connected component are updated (True by default)
extrapolate_reactive_limits
Mirror OLF's ``extrapolateReactiveLimits`` provider parameter (on by default):
a unit whose active power lies outside the P range of its reactive capability
curve has limits linearly extrapolated from the curve's end segment, where
pypowsybl's ``min_q_at_p`` / ``max_q_at_p`` clamp to the end point. Set it to
what the reference solve used, or a unit switched at an extrapolated limit
reads as a visible distance from its limit (see
:func:`_extrapolate_curve_limits`).
bake_saturated_voltage_control
Also freeze, at its limit, a generator (or a voltage-mode SVC) whose reactive
output sits at a Q limit although the reference solve held its target voltage
(a PV unit exactly saturated, to ``_Q_SATURATED_HELD_TOL_MVAR``). The base case is
unchanged, but any change of the grid asking it for more reactive power would make
OLF switch it to PQ anyway; kept regulating, it reports a reactive-limit violation
for almost every contingency. A held unit with more headroom than that is still
regulating and stays so. ``False`` (default) keeps every held unit regulating, as
OLF did.
bake_hvdc_ac_emulation_limits
Turn an angle-droop hvdc line OLF saturated at its active power limit into a
fixed setpoint at that limit (see :func:`_bake_hvdc_ac_emulation_limits`).
Left in AC emulation, a loop-free solve lets it transmit beyond its limit.
return_details
Return a :class:`BakeResult` rather than the :class:`pandas.Index` described
below: ``can_be_pv`` is that same index, and ``can_participate_slack`` holds the
generators (and batteries) left out of the slack ONLY because OLF capped them at
an active limit (``max_p`` for a positive reference mismatch, ``min_p`` for a
negative one) -- the ones OLF lets take a share again of a mismatch of the other
sign. Hand it to ``init_from_pypowsybl(can_participate_slack=...)`` so that
lightsim2grid's redistribution pre-pass counts them, away from their limit. A unit
excluded for one of OLF's own ``checkActivePowerControl`` reasons is not in it.
``can_participate_slack_overshoot`` says how far beyond its limit each of them was
(``init_from_pypowsybl(can_participate_slack_overshoot=...)``), and
``hvdc_ac_emulation_frozen`` holds the angle-droop hvdc lines frozen at their limit
(``init_from_pypowsybl(hvdc_ac_emulation_frozen=...)``, for the check of their release).
Returns
-------
pandas.Index
The ids of the elements this bake froze out of voltage control that an outer loop
would switch (back) to it:
* the generators it froze as PQ *at a reactive limit* (the reactive-limit step,
the exactly saturated ones included when ``bake_saturated_voltage_control`` is
set): what OLF's ``ReactiveLimits`` loop pinned, and what it would release again
on a grid asking them for less;
* the VSC converter stations it froze as PQ at a reactive limit, by the generators'
rule (reported on their hvdc line, ``side`` the station's end);
* the voltage-mode static var compensators it froze to fixed-Q at the edge of their
susceptance range, by the same rule (see :func:`_bake_svc_saturation`);
* the static var compensators whose standby automaton it left idle (frozen to
fixed-Q, see :func:`_bake_svc_standby`): what OLF's
``MonitoringVoltageOuterLoop`` would switch to voltage control, should the
voltage of their regulated bus leave the automaton's thresholds.
Hand it to ``init_from_pypowsybl(can_be_pv=...)`` so that lightsim2grid's physical
checks report such a switch (``LOW_VOLTAGE_AT_MIN_Q`` / ``HIGH_VOLTAGE_AT_MAX_Q``
on a generator or a frozen SVC, ``LOW_VOLTAGE_SVC_STANDBY`` /
``HIGH_VOLTAGE_SVC_STANDBY`` on an idle standby SVC -- the one whose
``standbyAutomaton`` still says ``standby``: the bake marks a standby SVC it
switched on as no longer standby, as OLF's automaton never goes back). IIDM ids are unique across element types, so the two never clash. The
generators switched off for another reason (not started, a reactive range too
small, an implausible target, a target not held) are not in it. Empty when
``bake_reactive_limits`` is off, or on an already-baked network.
Notes
-----
Operates in place and is idempotent on an already-baked network. The
voltage-regulation flag is *not* used as a switch signal: OLF does not flip
it in IIDM, so PV->PQ is detected from the realized Q sitting at a limit.
"""
df_bus = _get_buses(network)
pinned = pd.Index([], dtype=object)
if bake_taps:
_bake_taps_and_sections(network, keep_only_main_comp, df_bus)
hvdc_frozen = pd.Index([], dtype=object)
if bake_hvdc_ac_emulation_limits:
hvdc_frozen = _bake_hvdc_ac_emulation_limits(network, keep_only_main_comp, df_bus)
if bake_reactive_limits:
pinned = _bake_reactive_limit_switches(
network, keep_only_main_comp, bake_generator_voltage_control_discards,
extrapolate_reactive_limits, bake_saturated_voltage_control, df_bus
)
capped = pd.Index([], dtype=object)
overshoot = pd.Series(dtype=float)
if bake_active_power:
capped, overshoot = _bake_active_power(
network,
balance_on_loads=balance_on_loads,
load_power_factor_constant=load_power_factor_constant,
keep_only_main_comp=keep_only_main_comp,
bake_active_power_control_participation=bake_active_power_control_participation,
df_bus=df_bus
)
if bake_remote_voltage_control:
_bake_remote_voltage_control(network, keep_only_main_comp, df_bus)
if return_details:
return BakeResult(can_be_pv=pinned, can_participate_slack=capped,
can_participate_slack_overshoot=overshoot,
hvdc_ac_emulation_frozen=hvdc_frozen)
return pinned
class BakeResult(NamedTuple):
"""What :func:`bake_outer_loops` returns with ``return_details=True``."""
#: the elements frozen out of voltage control that an outer loop would switch
#: (back) to it -- what ``bake_outer_loops`` returns by default
can_be_pv: pd.Index
#: the generators and batteries left out of the slack only because OLF capped them
#: at an active limit -- for ``init_from_pypowsybl(can_participate_slack=...)``
can_participate_slack: pd.Index
#: how far beyond that limit each of them was in the reference distribution, MW (> 0 above
#: an upper limit, < 0 below a lower one, indexed
#: like ``can_participate_slack``) -- for
#: ``init_from_pypowsybl(can_participate_slack_overshoot=...)``
can_participate_slack_overshoot: pd.Series = None
#: the angle-droop hvdc lines this bake froze at their active power limit (see
#: ``_bake_hvdc_ac_emulation_limits``) -- for
#: ``init_from_pypowsybl(hvdc_ac_emulation_frozen=...)``, which opens them to the check
#: of their release
hvdc_ac_emulation_frozen: pd.Index = None
def _bake_taps_and_sections(network, keep_only_main_comp=True, df_bus=None):
# Ratio tap changers (transformer voltage control outer loop).
df_bus = _get_buses(network) if df_bus is None else df_bus
rtc = network.get_ratio_tap_changers(
attributes=["tap", "solved_tap_position", "regulating"]
)
if len(rtc):
# Only adopt the solved position where the changer was actually
# regulating AND a solved position exists. ``solved_tap_position`` is
# NaN when the changer did not participate in an outer loop; copying it
# blindly would destroy the input tap.
keep = rtc["regulating"] & rtc["solved_tap_position"].notna()
if keep.any():
upd = pd.DataFrame(index=rtc.index[keep])
upd["tap"] = rtc["solved_tap_position"][keep].astype(int)
# upd["regulating"] = False
network.update_ratio_tap_changers(upd)
# Phase tap changers (phase-shifter regulation outer loop).
ptc = network.get_phase_tap_changers(
attributes=["tap", "solved_tap_position", "regulating"]
)
if len(ptc):
keep = ptc["regulating"] & ptc["solved_tap_position"].notna()
if keep.any():
upd = pd.DataFrame(index=ptc.index[keep])
upd["tap"] = ptc["solved_tap_position"][keep].astype(int)
# upd["regulating"] = False
network.update_phase_tap_changers(upd)
# Shunt compensators (shunt voltage control outer loop).
sh = network.get_shunt_compensators(
attributes=[
"section_count",
"solved_section_count",
"voltage_regulation_on",
"connected",
"bus_id"
]
)
if keep_only_main_comp:
sh = _keep_only_main_comp(sh, df_bus)
if len(sh):
keep = sh["voltage_regulation_on"] & sh["solved_section_count"].notna()
if keep.any():
upd = pd.DataFrame(index=sh.index[keep])
upd["section_count"] = sh["solved_section_count"][keep].astype(int)
upd["voltage_regulation_on"] = False
network.update_shunt_compensators(upd)
def _bake_hvdc_ac_emulation_limits(network, keep_only_main_comp=True, df_bus=None):
"""Turn every angle-droop ("AC emulation") hvdc line OLF saturated into a fixed
setpoint at its limit.
OLF's ``AcHvdcAcEmulationLimits`` outer loop caps the active power the sending
converter takes from the AC grid at the line's limit in that direction: the
``hvdcOperatorActivePowerRange`` extension when the line carries it, ``max_p``
otherwise (see ``_hvdc_pmax_per_direction``). The loop-free parameters drop that
loop, so the line goes back to ``p0 + k . (theta_1 - theta_2)`` and transmits
beyond its limit; lightsim2grid does the same.
A line is saturated when its sending converter (the station taking power from the
grid, ``p > 0`` in the receptor convention) realized its limit within
``_HVDC_P_LIMIT_TOL_MW``. It is then baked as OLF solved it: droop switched off,
``target_p`` at the limit, ``converters_mode`` with the sending side as rectifier
(a fixed-setpoint line's ``target_p`` is what its rectifier takes from the grid).
Returns the ids of the hvdc lines baked.
"""
df_bus = _get_buses(network) if df_bus is None else df_bus
try:
droop = network.get_extensions("hvdcAngleDroopActivePowerControl")
except Exception:
# extension tables may be unavailable on (very) old pypowsybl versions
return pd.Index([], dtype=object)
if not len(droop):
return pd.Index([], dtype=object)
hvdc = network.get_hvdc_lines(attributes=["converter_station1_id", "converter_station2_id", "max_p"])
hvdc = hvdc[hvdc.index.isin(droop.index[droop["enabled"].astype(bool)])]
if not len(hvdc):
return pd.Index([], dtype=object)
stations = pd.concat([
network.get_vsc_converter_stations(attributes=["p", "connected", "bus_id"]),
network.get_lcc_converter_stations(attributes=["p", "connected", "bus_id"]),
])
if keep_only_main_comp:
stations_in = stations.index.isin(_keep_only_main_comp(stations, df_bus).index)
else:
stations_in = stations["connected"].to_numpy(bool)
stations_in = pd.Series(stations_in, index=stations.index)
st1 = stations.loc[hvdc["converter_station1_id"].to_numpy()]
st2 = stations.loc[hvdc["converter_station2_id"].to_numpy()]
in_service = stations_in.loc[st1.index].to_numpy() & stations_in.loc[st2.index].to_numpy()
max_p = hvdc["max_p"].to_numpy(float)
pmax_1to2, pmax_2to1 = _hvdc_pmax_per_direction(network, hvdc.index, np.where(np.isfinite(max_p), max_p, np.inf))
p1 = st1["p"].to_numpy(float)
p2 = st2["p"].to_numpy(float)
from_1 = p1 > 0. # side 1 takes the power from the grid: the flow goes 1 -> 2
sent = np.where(from_1, p1, p2)
limit = np.where(from_1, pmax_1to2, pmax_2to1)
mask = in_service & np.isfinite(sent) & np.isfinite(limit) & (sent >= limit - _HVDC_P_LIMIT_TOL_MW)
if mask.any():
ids = hvdc.index[mask]
upd = pd.DataFrame(index=ids)
upd["target_p"] = limit[mask]
upd["converters_mode"] = np.where(from_1[mask], "SIDE_1_RECTIFIER_SIDE_2_INVERTER",
"SIDE_1_INVERTER_SIDE_2_RECTIFIER")
network.update_hvdc_lines(upd)
network.update_extensions("hvdcAngleDroopActivePowerControl", id=list(ids), enabled=[False] * len(ids))
return pd.Index(hvdc.index[mask], dtype=object)
def _resolve_regulated_bus(network, own_bus, regulated_element_id):
"""Bus-view id of the bus each element regulates, as a ``pandas.Series`` indexed
like ``own_bus``: the element's own bus where it regulates locally, or where the
remote element cannot be resolved.
Element-type agnostic (a generator's ``regulated_element_id`` column and a
battery's ``voltageRegulation`` extension say the same thing), so both go through
it -- see :func:`_generator_regulated_bus` and :func:`_bake_battery_voltage_control`.
"""
rel = regulated_element_id.reindex(own_bus.index).fillna("").astype(str)
reg_bus = own_bus.copy()
remote = (rel != "") & (rel != rel.index.to_series())
if not remote.any():
return reg_bus
from ._aux_common import _aux_regulated_bus_view_ids
try:
resolved = _aux_regulated_bus_view_ids(network, rel[remote].to_numpy())
except RuntimeError:
return reg_bus
resolved = pd.Series(resolved, index=rel.index[remote])
reg_bus.loc[remote] = resolved.where(resolved != "", own_bus[remote])
return reg_bus
def _generator_regulated_bus(network, gen):
"""Bus-view id of the bus each generator in ``gen`` regulates (its own bus for
a local controller), as a ``pandas.Series`` indexed like ``gen``.
Uses pypowsybl's own ``regulated_bus_id`` when the installed version provides
it (it resolves a ``regulated_element_id`` that is a busbar section, a
transformer terminal, another generator, ...), else falls back to resolving
``regulated_element_id`` through the bus-connected elements
(:func:`_resolve_regulated_bus`), then to the generator's own bus.
"""
own = gen["bus_id"]
try:
rb = network.get_generators(attributes=["regulated_bus_id"])["regulated_bus_id"]
rb = rb.reindex(gen.index)
return rb.where(rb.notna() & (rb != ""), own)
except Exception:
pass
rel = gen["regulated_element_id"] if "regulated_element_id" in gen.columns else pd.Series("", index=gen.index)
return _resolve_regulated_bus(network, own, rel)
def _target_v_held(network, reg_bus, target_v, df_bus=None):
"""Boolean ``pandas.Series`` (indexed like ``reg_bus``): the reference solve held
``target_v`` at the bus of ``reg_bus`` -- the empirical signature of a unit OLF
actually voltage-controlled (see ``_TARGET_V_HELD_TOL_PU``). ``False`` where the
regulated bus has no solved voltage.
The decision is about the regulated bus, not about the element holding it, so
generators and batteries share it (their regulation flag and target live in
different places, what to do with the answer is all that differs).
"""
df_bus = _get_buses(network) if df_bus is None else df_bus
buses = df_bus.reindex(reg_bus.to_numpy())
v = buses["v_mag"].to_numpy(float)
nom = buses["nominal_v"].to_numpy(float)
with np.errstate(invalid="ignore", divide="ignore"):
dv = np.abs(v - np.asarray(target_v, dtype=float)) / nom
return pd.Series(np.isfinite(dv) & (dv < _TARGET_V_HELD_TOL_PU), index=reg_bus.index)
def _generator_target_v_held(network, gen, df_bus=None, reg_bus=None):
""":func:`_target_v_held` for the generators of ``gen``, which must carry
``target_v``, ``bus_id`` and (for the fallback resolution) ``regulated_element_id``.
``reg_bus``, when given, is :func:`_generator_regulated_bus` already resolved."""
if reg_bus is None:
reg_bus = _generator_regulated_bus(network, gen)
return _target_v_held(network, reg_bus.reindex(gen.index), gen["target_v"], df_bus)
def _generator_regulated_nominal_v(network, gen, df_bus=None, reg_bus=None):
"""Nominal voltage (kV) of the bus each generator in ``gen`` regulates, as a
numpy array aligned with ``gen`` (NaN where unresolved)."""
if reg_bus is None:
reg_bus = _generator_regulated_bus(network, gen)
df_bus = _get_buses(network) if df_bus is None else df_bus
return df_bus["nominal_v"].reindex(reg_bus.reindex(gen.index).to_numpy()).to_numpy(float)
def _bake_generator_not_started(network, keep_only_main_comp=True, held=None, df_bus=None):
"""Freeze a voltage-regulating generator dispatched at (approximately) 0 MW,
with a strictly positive minimum active power, to fixed-Q (PQ) -- mirroring
PowSyBl OpenLoadFlow's own generator setup rule (default-on parameter
``generatorsWithZeroMwTargetAreNotStarted``,
``AbstractLfGenerator.checkIfGeneratorStartedForVoltageControl``): such a
generator is declared unable to legitimately run at 0 MW (``min_p > 0``), so
OLF treats it as "not started" and never sets it up as a voltage-controlling
PV bus in the first place -- regardless of its ``voltage_regulator_on`` /
``target_v`` attributes, which read as if it were actively regulating. A
generator with ``min_p <= 0`` (legitimately allowed to sit at 0 MW, e.g. a
curtailed renewable) is NOT affected -- OLF keeps it on voltage control.
``lightsim2grid``'s own C++ analogue (``GeneratorContainer::is_pseudo_off``,
gated by ``turnedoff_no_pv`` / ``LightSimBackend(turned_off_pv=False)``) does
not check ``min_p`` yet (see the CHANGELOG.rst TODO) and is off by default
anyway (Grid2Op semantics: an agent redispatching a generator to ~0 MW
mid-episode should not silently also drop its voltage support) -- so this
OLF-specific case is instead resolved here, on the pypowsybl-loading path
only, the same way ``_bake_svc_standby`` resolves the SVC standby automaton.
Runs before the reactive-limit-switch check below: a generator resolved to PQ
here is already frozen and skipped there (it only looks at
``voltage_regulator_on == True``).
``held`` (optional, see :func:`_generator_target_v_held`) is the set of
generators whose target voltage the reference solve actually held: those are
never frozen here, whatever this rule says -- the result is the authority on
what OLF did.
"""
df_bus = _get_buses(network) if df_bus is None else df_bus
gen = network.get_generators(
attributes=["voltage_regulator_on", "target_p", "min_p", "q", "connected", "bus_id"]
)
if keep_only_main_comp:
gen = _keep_only_main_comp(gen, df_bus)
not_started = (
gen["voltage_regulator_on"]
& (gen["target_p"].abs() < _ZERO_P_TOL)
& (gen["min_p"] > _ZERO_P_TOL)
)
if held is not None:
not_started &= ~held.reindex(gen.index).fillna(False).astype(bool)
if not not_started.any():
return
upd = pd.DataFrame(index=gen.index[not_started])
# result "q" is load/receptor convention; Generator.target_q is generator convention
upd["target_q"] = -gen["q"].to_numpy()[not_started]
upd["voltage_regulator_on"] = False
network.update_generators(upd)
def _generator_max_reactive_range(network, gen_index):
"""OLF's own default ``reactiveRangeCheckMode`` is ``MAX``: the widest
``max_q - min_q`` across the whole active-power range of the reactive
capability curve for a CURVE-kind generator, or simply ``max_q - min_q``
for a MIN_MAX (fixed box) generator. Returns a ``pandas.Series`` of ranges
(MVAr), indexed like ``gen_index``, ``NaN`` for any id not found.
"""
rng = pd.Series(np.nan, index=gen_index)
if not len(gen_index):
return rng
box = network.get_generators(attributes=["reactive_limits_kind", "min_q", "max_q"])
box = box.loc[box.index.intersection(gen_index)]
is_box = box["reactive_limits_kind"] == "MIN_MAX"
rng.loc[box.index[is_box]] = (box["max_q"] - box["min_q"])[is_box]
curve_ids = box.index[~is_box]
if len(curve_ids):
pts = network.get_reactive_capability_curve_points()
# pts is indexed on a (id, num) MultiIndex -- intersecting it directly against
# a flat Index of generator ids matches nothing, since a tuple never equals a
# bare id; filter on the first level instead.
pts = pts.loc[pts.index.get_level_values(0).isin(curve_ids)]
if len(pts):
pt_range = pts["max_q"] - pts["min_q"]
rng.update(pt_range.groupby(level=0).max())
return rng
def _bake_generator_voltage_control_discards(network, keep_only_main_comp=True, held=None, df_bus=None,
reg_bus=None):
"""Freeze a voltage-regulating generator to fixed-Q when PowSyBl OLF's own
consistency checks (``AbstractLfGenerator.checkVoltageControlConsistency``)
would have discarded it from voltage control for a reason other than "not
started" (handled separately by :func:`_bake_generator_not_started`, which
must run before this so its frozen generators are excluded here):
* too small a reactive range (``checkIfReactiveRangesAreLargeEnoughForVoltageControl``,
see :func:`_generator_max_reactive_range` and ``_MIN_REACTIVE_RANGE_MVAR``);
* an implausible target voltage (``checkTargetV``, see
``_MIN_PLAUSIBLE_TARGET_V_PU`` / ``_MAX_PLAUSIBLE_TARGET_V_PU``).
Like ``_bake_generator_not_started``, these generators never actually reached
voltage control in the reference (outer-loop) run: OLF falls back to a fixed-Q
injection at the raw IIDM ``target_q`` (``LfGeneratorImpl.getTargetQ()``), *not*
at any computed value -- so the realized ``q`` from the reference solve already
equals that fixed output, and freezing to it here is exact. Without this,
lightsim2grid -- which has no equivalent of these OLF-specific plausibility
screens -- would treat such a generator as a normal PV bus after baking.
The target-voltage plausibility is judged in per unit of the **regulated**
bus's nominal voltage (OLF's ``checkTargetV`` does the same): a 24 kV unit
regulating the 400 kV side of its step-up transformer legitimately carries a
~400 kV ``target_v``, which read as ~16 pu of its own terminal and got it
wrongly frozen by an earlier version of this check.
``held`` (optional, see :func:`_generator_target_v_held`): generators whose
target the reference solve actually held are never frozen here.
"""
df_bus = _get_buses(network) if df_bus is None else df_bus
gen = network.get_generators(
attributes=["voltage_regulator_on", "target_v", "q", "voltage_level_id", "connected", "bus_id",
"regulated_element_id"]
)
if keep_only_main_comp:
gen = _keep_only_main_comp(gen, df_bus)
reg = gen[gen["voltage_regulator_on"]]
if not len(reg):
return
reg_nominal_v = _generator_regulated_nominal_v(network, reg, df_bus, reg_bus)
max_range = _generator_max_reactive_range(network, reg.index).to_numpy()
too_small_range = max_range < _MIN_REACTIVE_RANGE_MVAR
with np.errstate(invalid="ignore", divide="ignore"):
target_v_pu = reg["target_v"].to_numpy() / reg_nominal_v
implausible_v = (
(reg_nominal_v > _MIN_NOMINAL_V_FOR_TARGET_V_CHECK_KV)
& ((target_v_pu < _MIN_PLAUSIBLE_TARGET_V_PU) | (target_v_pu > _MAX_PLAUSIBLE_TARGET_V_PU))
)
mask = too_small_range | implausible_v
if held is not None:
held_reg = held.reindex(reg.index).fillna(False).to_numpy(bool)
# "held" is a property of the regulated bus: a unit with too small a range
# sharing it with a controller OLF keeps (a large enough range) reads as held
# although that other unit is the one holding it -- OLF discarded this one
# all the same (and with it the reactive capability it would add to the bus)
reg_bus_of = (_generator_regulated_bus(network, reg) if reg_bus is None
else reg_bus.reindex(reg.index)).to_numpy()
kept_buses = set(reg_bus_of[~too_small_range & ~implausible_v])
shares_with_kept = np.array([b in kept_buses for b in reg_bus_of], dtype=bool)
mask &= ~held_reg | (too_small_range & shares_with_kept)
if not mask.any():
return
upd = pd.DataFrame(index=reg.index[mask])
upd["target_q"] = -reg["q"].to_numpy()[mask]
upd["voltage_regulator_on"] = False
network.update_generators(upd)
def _bake_remote_control_bus_conflicts(network, keep_only_main_comp=True, held=None, df_bus=None):
"""Freeze a *remotely*-regulating generator to fixed-Q when its OWN bus
already hosts another connected, *locally* voltage-regulating generator.
Physical reason: if a co-located generator locally pins this bus's voltage
(holding it at its own target, within its own reactive limits), that bus's
voltage is not a free network unknown from the remote controller's point of
view -- AC power flow couples buses purely through voltage phasors, so how
the *combined* reactive injection at that bus splits between the two
co-located generators has *zero* effect on any other bus's voltage,
including the one the second generator is trying to remotely control. Its
own voltage target is therefore unreachable regardless of its dispatched Q.
Verified on a real grid carrying this exact configuration: solving the
baked (loop-free) network with OLF, with BOTH generators still nominally
regulating, reproduces almost exactly the voltage obtained by freezing the
remote one to its realized Q (much closer than OLF gets to the -- provably
unreachable -- raw remote target itself), showing OLF itself discards the
remote controller rather than actually achieving its target through free
reactive power.
lightsim2grid's own C++ voltage-control extension has no equivalent
discard: a lone remote controller sharing a bus with a local one produces a
genuinely singular Jacobian (the remote controller's own reactive-injection
unknown ends up with no equation to pair with) which either crashes
(``ErrorType.SolverFactor``, if the shared bus is classified as a
distributed-slack participant) or raises ``LSGrid::fill_voltage_control_
solver_data``'s own "not supported in v1" error (if it lands on an ordinary
PV bus) -- so this must be resolved before ``init()`` runs.
Runs after :func:`_bake_generator_not_started` and
:func:`_bake_generator_voltage_control_discards`: a co-located generator
already frozen there (e.g. "not started", or discarded for too small a
reactive range) no longer counts as "locally regulating", so a remote
generator sharing its bus is correctly left alone once the true conflict is
resolved.
"""
df_bus = _get_buses(network) if df_bus is None else df_bus
gen = network.get_generators(
attributes=["voltage_regulator_on", "regulated_element_id", "q", "connected", "bus_id"]
)
if keep_only_main_comp:
gen = _keep_only_main_comp(gen, df_bus)
reg = gen["regulated_element_id"].fillna("")
is_remote = gen["voltage_regulator_on"] & (reg != "") & (reg != gen.index)
is_local = gen["voltage_regulator_on"] & ~is_remote
if not is_remote.any() or not is_local.any():
return
local_buses = set(gen.loc[is_local, "bus_id"])
conflict = is_remote & gen["bus_id"].isin(local_buses)
if held is not None:
conflict &= ~held.reindex(gen.index).fillna(False).astype(bool)
if not conflict.any():
return
upd = pd.DataFrame(index=gen.index[conflict])
upd["target_q"] = -gen["q"].to_numpy()[conflict]
upd["voltage_regulator_on"] = False
network.update_generators(upd)
def _bake_generator_voltage_control_not_held(network, keep_only_main_comp=True, held=None, df_bus=None):
"""Catch-all: freeze to fixed-Q (its realized reactive output) every
voltage-regulating generator whose target voltage the reference solve did
NOT hold (see :func:`_generator_target_v_held`), whatever the reason --
a reactive-limit switch the tolerance-based rule missed, a generator on a
bus below ``generatorVoltageControlMinNominalVoltage``, a voltage-control
discard for a rule not reproduced here, a controller OLF merged into another
one's ... The realized ``q`` is exactly what OLF injected, so the freeze is
exact; and a generator OLF *did* control keeps regulating. Only generators
with a solved (finite) reactive output are touched.
"""
df_bus = _get_buses(network) if df_bus is None else df_bus
gen = network.get_generators(
attributes=["voltage_regulator_on", "target_v", "q", "connected", "bus_id", "regulated_element_id"]
)
if keep_only_main_comp:
gen = _keep_only_main_comp(gen, df_bus)
if held is None:
held = _generator_target_v_held(network, gen, df_bus)
mask = (gen["voltage_regulator_on"] & gen["q"].notna()
& ~held.reindex(gen.index).fillna(False).astype(bool))
if not mask.any():
return
upd = pd.DataFrame(index=gen.index[mask])
upd["target_q"] = -gen["q"].to_numpy()[mask]
upd["voltage_regulator_on"] = False
network.update_generators(upd)
def _bake_generator_target_q_forced_in_limits(network, keep_only_main_comp=True, df_bus=None):
"""Write the realized reactive output into ``target_q`` for every connected,
non-regulating generator whose reference solve did not inject its ``target_q``.
OLF's default ``forceTargetQInReactiveLimits`` clamps a PQ generator's target into
its reactive capability at its active power (the case seen on real grid snapshots:
a unit at 0 MW whose curve starts above 0 MVAr, with ``target_q = 0``). The loop-free
parameters turn the reactive limits off, which turns the clamp off with them, and
lightsim2grid never clamps: without this both inject the raw target, and the
voltages of the low-voltage side it feeds are visibly off. The realized value is what
OLF injected, so the rewrite is exact, and it also covers any other reason a PQ
injection moved.
"""
df_bus = _get_buses(network) if df_bus is None else df_bus
gen = network.get_generators(attributes=["voltage_regulator_on", "target_q", "q", "connected", "bus_id"])
if keep_only_main_comp:
gen = _keep_only_main_comp(gen, df_bus)
q_gen = -gen["q"] # result column is load convention; target_q is generator convention
moved = (~gen["voltage_regulator_on"].astype(bool) & q_gen.notna()
& ((q_gen - gen["target_q"]).abs() > _TARGET_Q_TOL_MVAR))
if not moved.any():
return
network.update_generators(pd.DataFrame({"target_q": q_gen[moved].to_numpy()}, index=gen.index[moved]))
def _bake_battery_voltage_control(network, keep_only_main_comp=True, df_bus=None):
""":func:`_bake_generator_voltage_control_not_held`, for the batteries carrying an
IIDM ``voltageRegulation`` extension (OLF runs them as PV; the converter models them
as voltage-regulating storage units, see
``_aux_add_storage._aux_battery_voltage_regulation``): a battery whose target voltage
the reference solve did not hold (switched at a reactive limit, discarded, ...) gets
the extension switched off and its realized reactive output as fixed ``target_q``.
The decision itself -- :func:`_target_v_held` on the regulated bus -- is the shared
one. What does not merge is the plumbing around it: a battery's regulation flag,
target voltage and regulated element live in an extension frame rather than in
columns of ``get_batteries()``, and switching it off is an ``update_extensions`` call
rather than an ``update_batteries`` one.
"""
try:
vr = network.get_extensions("voltageRegulation")
except Exception:
return
if vr is None or not len(vr) or "voltage_regulator_on" not in vr.columns:
return
bat = network.get_batteries(attributes=["q", "connected", "bus_id"])
if keep_only_main_comp:
df_bus = _get_buses(network) if df_bus is None else df_bus
bat = _keep_only_main_comp(bat, df_bus)
vr = vr.reindex(bat.index)
on = vr["voltage_regulator_on"].fillna(False).astype(bool)
if not on.any():
return
ids = bat.index[on.to_numpy()]
reg = vr.loc[ids, "regulated_element_id"] if "regulated_element_id" in vr.columns \
else pd.Series("", index=ids)
reg_bus = _resolve_regulated_bus(network, bat.loc[ids, "bus_id"], reg)
held = _target_v_held(network, reg_bus, vr.loc[ids, "target_v"], df_bus).to_numpy()
freeze = ~held & bat.loc[ids, "q"].notna().to_numpy()
if not freeze.any():
return
frozen = ids[freeze]
network.update_extensions("voltageRegulation", pd.DataFrame({"voltage_regulator_on": False}, index=frozen))
network.update_batteries(pd.DataFrame({"target_q": -bat.loc[frozen, "q"].to_numpy()}, index=frozen))
def _bus_still_regulating(gen, at_limit):
"""Boolean ``pandas.Series`` (indexed like ``gen``): another voltage-regulating
generator of the same bus is not ``at_limit``. OLF switches a whole bus, not one of
its units: such a unit at its limit was only clamped when OLF split the bus' reactive
power among its units, the bus (and the unit) still regulating."""
regulating = gen["voltage_regulator_on"].astype(bool)
n_free = (regulating & ~at_limit).astype(int).groupby(gen["bus_id"]).transform("sum")
return n_free > 0
def _switched_group_members(network, gen, q_gen, reg_bus=None):
"""Boolean ``pandas.Series`` (indexed like ``gen``): a voltage-regulating
generator whose realized reactive output sits *exactly* at a limit (absolute
tolerance only, a PQ unit injects its limit to the digit) while at least one
other generator regulating the same bus is still inside its range -- the
signature of a unit OLF switched out of a shared control group, whose regulated
bus nevertheless reads as held. Not one whose own bus still regulates (see
`_bus_still_regulating`)."""
regulating = gen["voltage_regulator_on"].astype(bool)
qmin, qmax = _reactive_limits(gen)
exact = regulating & ((q_gen >= qmax - _Q_LIMIT_TOL_ABS) | (q_gen <= qmin + _Q_LIMIT_TOL_ABS))
exact &= ~_bus_still_regulating(gen, exact)
if not exact.any():
return exact
if reg_bus is None:
reg_bus = _generator_regulated_bus(network, gen)
reg_bus = reg_bus.reindex(gen.index)
n_free = (regulating & ~exact).astype(int).groupby(reg_bus).transform("sum")
return exact & (n_free > 0)
def _extrapolate_curve_limits(network, df: pd.DataFrame):
"""Return ``df`` with ``min_q_at_p`` / ``max_q_at_p`` replaced, for every row whose
realized active power (``-p``) lies outside the P range of its reactive capability
curve, by the linear extrapolation of the curve's end segment on that side.
That is what OLF evaluates with its default ``extrapolateReactiveLimits``, where
pypowsybl's columns clamp to the end point. On real grid snapshots, units running
below the P range of their curve are switched at the *extrapolated* limit, which sits
a visible distance from the clamped one -- far enough that the freeze below would
otherwise bake the wrong value. Rows inside their curve, without a curve, or with
fewer than two points are untouched.
"""
if not len(df) or "p" not in df.columns or "min_q_at_p" not in df.columns:
return df
try:
pts = network.get_reactive_capability_curve_points()
except Exception: # noqa: BLE001 - no curve support in this pypowsybl
return df
pts = pts.loc[pts.index.get_level_values(0).isin(df.index)]
if not len(pts):
return df
# one vectorised pass over every curve (a per-curve loop dominates the whole bake on
# a large grid): sort the points by (element, p), then read each curve's first two
# and last two points by position
ids = pts.index.get_level_values(0).to_numpy()
p_pt = pts["p"].to_numpy(float)
codes = pd.factorize(ids)[0]
order = np.lexsort((p_pt, codes)) # stable: points of equal p keep their curve order
ids, codes, p_pt = ids[order], codes[order], p_pt[order]
qmin_pt = pts["min_q"].to_numpy(float)[order]
qmax_pt = pts["max_q"].to_numpy(float)[order]
start = np.flatnonzero(np.r_[True, codes[1:] != codes[:-1]])
count = np.diff(np.r_[start, len(ids)])
start, count = start[count >= 2], count[count >= 2]
if not len(start):
return df
el_ids = ids[start]
# result column is load convention; curves are in generator convention
power = -df["p"].reindex(el_ids).to_numpy(float)
below = power < p_pt[start]
above = power > p_pt[start + count - 1]
# the end segment on the side the unit lies (NaN power is neither below nor above)
i1 = np.where(below, start, start + count - 2)
i2 = i1 + 1
p1, p2 = p_pt[i1], p_pt[i2]
keep = (below | above) & (p2 != p1)
if not keep.any():
return df
i1, i2, p1, p2, power = i1[keep], i2[keep], p1[keep], p2[keep], power[keep]
df = df.copy()
rows = df.index.get_indexer(el_ids[keep])
for col, q in (("min_q_at_p", qmin_pt), ("max_q_at_p", qmax_pt)):
vals = df[col].to_numpy(float, copy=True)
vals[rows] = q[i1] + (q[i2] - q[i1]) * (power - p1) / (p2 - p1)
df[col] = vals
return df
def _bake_reactive_limit_switches(
network,
keep_only_main_comp=True,
bake_generator_voltage_control_discards=True,
extrapolate_reactive_limits=True,
bake_saturated_voltage_control=False,
df_bus=None):
# What OLF actually did with each generator's voltage control, read off the
# reference solve itself: every rule below defers to it (a generator whose
# target was held is never frozen, one whose target was not is always frozen
# in the end), the rules only document *why* OLF dropped a control.
df_bus = _get_buses(network) if df_bus is None else df_bus
gen0 = network.get_generators(
attributes=["voltage_regulator_on", "target_v", "connected", "bus_id", "regulated_element_id"])
if keep_only_main_comp:
gen0 = _keep_only_main_comp(gen0, df_bus)
# resolved once: which bus a generator regulates is not something the bake changes
reg_bus = _generator_regulated_bus(network, gen0)
held = _generator_target_v_held(network, gen0, df_bus, reg_bus) & gen0["voltage_regulator_on"]
# first, while "not regulating" still means "PQ in the reference solve": the
# freezes below turn regulation off on units whose reported q is not what they
# inject (see _hit_qlimit), which this must not write back
_bake_generator_target_q_forced_in_limits(network, keep_only_main_comp, df_bus)
_bake_generator_not_started(network, keep_only_main_comp, held, df_bus)
if bake_generator_voltage_control_discards:
_bake_generator_voltage_control_discards(network, keep_only_main_comp, held, df_bus, reg_bus)
_bake_remote_control_bus_conflicts(network, keep_only_main_comp, held, df_bus)
gen = network.get_generators(
attributes=[
"voltage_regulator_on", "q", "p",
"min_q", "max_q", "min_q_at_p", "max_q_at_p",
"connected", "bus_id", "regulated_element_id"
]
)
if keep_only_main_comp:
gen = _keep_only_main_comp(gen, df_bus)
if extrapolate_reactive_limits:
gen = _extrapolate_curve_limits(network, gen)
mask, q_gen = _bound_at_qlimit(gen, gen["voltage_regulator_on"])
# a unit sitting at its Q limit while OLF still held its target is a PV bus
# exactly saturated, not a switched one: the relative tolerance of
# _q_limit_tol exists to catch a switched unit that settled a hair *inside*
# its limit, and that unit's voltage is free, hence off target.
# "held" is a property of the regulated bus, so it cannot tell apart the
# members of a group sharing one: a member exactly at its limit while another
# member is still inside its range was switched (OLF drops it from the group
# and the others keep the target), and the split it leaves behind decides the
# voltages behind each unit's step-up transformer.
# bake_saturated_voltage_control freezes the saturated ones too: at their limit to
# _Q_SATURATED_HELD_TOL_MVAR, not to the relative tolerance (a held unit with some
# headroom left is still regulating).
not_held = ~held.reindex(gen.index).fillna(False).astype(bool)
switched = _switched_group_members(network, gen, q_gen, reg_bus)
if bake_saturated_voltage_control:
qmin, qmax = _reactive_limits(gen)
saturated = (q_gen >= qmax - _Q_SATURATED_HELD_TOL_MVAR) | (q_gen <= qmin + _Q_SATURATED_HELD_TOL_MVAR)
saturated &= ~_bus_still_regulating(gen, saturated)
mask &= not_held | saturated | switched
else:
mask &= not_held | switched
pinned = gen.index[mask]
if mask.any():
upd = pd.DataFrame(index=pinned)
# the limit it was switched at rather than a misreported q (see _baked_q_at_limit)
upd["target_q"] = _baked_q_at_limit(gen, q_gen)[mask]
upd["voltage_regulator_on"] = False
network.update_generators(upd)
if bake_generator_voltage_control_discards:
# everything OLF dropped for a reason the rules above do not spell out
_bake_generator_voltage_control_not_held(network, keep_only_main_comp, held, df_bus)
_bake_battery_voltage_control(network, keep_only_main_comp, df_bus)
vsc = network.get_vsc_converter_stations(
attributes=[
"voltage_regulator_on", "q", "p",
"min_q", "max_q", "min_q_at_p", "max_q_at_p",
"connected", "bus_id"
]
)
if keep_only_main_comp:
vsc = _keep_only_main_comp(vsc, df_bus)
if extrapolate_reactive_limits:
vsc = _extrapolate_curve_limits(network, vsc)
frozen_vsc = pd.Index([], dtype=object)
if len(vsc):
mask, q_gen = _bound_at_qlimit(vsc, vsc["voltage_regulator_on"])
if mask.any():
upd = pd.DataFrame(index=vsc.index[mask])
upd["target_q"] = _baked_q_at_limit(vsc, q_gen)[mask]
upd["voltage_regulator_on"] = False
network.update_vsc_converter_stations(upd)
# like a generator frozen at a limit: what the loop would release again
frozen_vsc = pd.Index(vsc.index[mask], dtype=object)
idle_svc = _bake_svc_standby(network, keep_only_main_comp, df_bus)
saturated_svc = _bake_svc_saturation(network, keep_only_main_comp, df_bus,
bake_saturated_voltage_control)
# the generators and the SVCs this step froze AT A REACTIVE LIMIT (not the ones the
# other rules switched off), and the standby SVCs it left idle: the ones an outer loop
# would switch (back) to voltage control, see `bake_outer_loops`
return pinned.append(frozen_vsc).append(saturated_svc).append(idle_svc)
def _bake_svc_standby(network, keep_only_main_comp=True, df_bus=None):
"""Resolve an SVC's "standby automaton" (PowSyBl OLF's ``MonitoringVoltageOuterLoop``)
to the state the outer loop actually settled on.
OLF only builds the automaton for an SVC that regulates voltage (``regulating``, in
``VOLTAGE`` mode) and whose ``standbyAutomaton`` extension says ``standby=True``;
any other SVC ignores the extension. Such an SVC starts the outer loop as a
fixed-susceptance shunt (``b0``, no voltage control) rather than as a voltage
controller, and only switches to active voltage control -- targeting
``low_voltage_setpoint`` / ``high_voltage_setpoint`` -- once the voltage of the bus
it CONTROLS (its regulated bus, like OLF) crosses ``low_voltage_threshold`` /
``high_voltage_threshold``. Inside the deadband it stays a plain ``b0`` shunt: the
realized ``q`` there equals ``b0 * v_mag_kv ** 2`` to the digit (0 when, as commonly
configured, ``b0 == 0``), so freezing it to that realized value -- like a saturated
SVC -- reproduces the deadband state exactly. That is also how a switched-on one is
told apart: its output is whatever holds its setpoint, while the voltage it holds
usually sits inside the thresholds and says nothing.
Runs before ``_bake_svc_saturation``: an SVC resolved to VOLTAGE mode here (crossed a
threshold) is still eligible for the ordinary saturation freeze; an SVC resolved to
REACTIVE_POWER here is already frozen and the saturation check leaves it alone (it only
looks at ``regulation_mode == "VOLTAGE"``).
Returns the ids of the SVCs left idle (frozen to REACTIVE_POWER): the ones OLF would
still switch on, should the voltage of their regulated bus leave the thresholds.
"""
idle_ids = pd.Index([], dtype=object)
try:
automaton = network.get_extensions("standbyAutomaton")
except Exception: # noqa: BLE001 - extension unsupported / absent on old pypowsybl
return idle_ids
automaton = automaton[automaton["standby"]]
if not len(automaton):
return idle_ids
df_bus = _get_buses(network) if df_bus is None else df_bus
svc = network.get_static_var_compensators()
svc = svc.loc[svc.index.intersection(automaton.index)]
if keep_only_main_comp:
svc = _keep_only_main_comp(svc, df_bus)
# OLF only arms the automaton of an SVC regulating voltage
voltage_mode = svc["regulation_mode"].astype(str) == "VOLTAGE"
if "regulating" in svc.columns:
voltage_mode &= svc["regulating"].astype(bool)
svc = svc[voltage_mode]
automaton = automaton.loc[svc.index]
if not len(automaton):
return idle_ids
rel = svc["regulated_element_id"] if "regulated_element_id" in svc.columns \
else pd.Series("", index=svc.index)
reg_bus = _resolve_regulated_bus(network, svc["bus_id"], rel)
v_kv = df_bus["v_mag"].reindex(reg_bus.to_numpy()).to_numpy(float)
# whether OLF switched it on is read off its output, not off the voltage: once on,
# it holds its bus at a SETPOINT, which usually sits inside the thresholds. Idle, it
# is a plain b0 shunt at its own bus and produces exactly that (receptor convention:
# q = -b0 * V^2), to the digit; switched on, whatever holds the setpoint.
v_own = df_bus["v_mag"].reindex(svc["bus_id"].to_numpy()).to_numpy(float)
q_idle = -automaton["b0"].to_numpy(float) * v_own ** 2
q = svc["q"].to_numpy(float)
active = np.isfinite(q) & (np.abs(q - q_idle) > _TARGET_Q_TOL_MVAR)
# a regulated bus without a solved voltage: nothing to check a later switch against,
# so an idle one is frozen but not returned
solved = np.isfinite(v_kv)
if active.any():
upd = pd.DataFrame(index=automaton.index[active])
# the setpoint it holds: the nearer one (the low and the high one are often equal)
low_sp = automaton["low_voltage_setpoint"].to_numpy(float)[active]
high_sp = automaton["high_voltage_setpoint"].to_numpy(float)[active]
v_act = v_kv[active]
upd["target_v"] = np.where(np.abs(v_act - high_sp) < np.abs(v_act - low_sp), high_sp, low_sp)
upd["regulation_mode"] = "VOLTAGE"
network.update_static_var_compensators(upd)
# the automaton never goes back to standby: once switched on it is a plain voltage
# controller, and marking it so leaves "standby" meaning "idle" on the baked network
# (which is how `init_from_pypowsybl(can_be_pv=...)` tells the two kinds of SVC apart)
network.update_extensions("standbyAutomaton", pd.DataFrame(
{"standby": False}, index=pd.Index(automaton.index[active], name="id")))
idle_ids = automaton.index[~active]
if len(idle_ids):
# realized "q" (receptor convention, matches target_q) already equals b0 * v^2
svc_q = network.get_static_var_compensators(attributes=["q"]).loc[idle_ids, "q"]
upd = pd.DataFrame(index=idle_ids)
upd["target_q"] = svc_q
upd["regulation_mode"] = "REACTIVE_POWER"
network.update_static_var_compensators(upd)
return pd.Index(automaton.index[~active & solved], dtype=object)
def _bake_svc_saturation(network, keep_only_main_comp=True, df_bus=None,
bake_saturated_voltage_control=False):
"""Freeze a VOLTAGE-mode SVC whose realized reactive output sits at (or beyond)
its voltage-dependent susceptance envelope to fixed-Q (REACTIVE_POWER mode),
with the same rule as ``_bake_reactive_limit_switches`` for generators.
Unlike a generator's fixed Q box, an SVC's reactive range is
``Q(V) = b * V^2`` (``b`` in ``b_min``..``b_max``, in Siemens, shifted by the ``b0`` of
its standby automaton when it carries one, see ``_svc_standby_b0``): recompute
``qmin``/``qmax`` in MVAr at the SVC's own solved terminal voltage before
comparing against the realized ``q``, within ``_q_limit_tol``.
As for a generator, that tolerance only proposes a candidate: an SVC whose
regulated bus the reference solve held at its ``target_v`` (``_target_v_held``)
was voltage-controlled, sitting a hair inside its limit, and is left regulating
-- unless it sits exactly at its limit while another controller of the same
bus (a regulating generator or SVC) is still inside its range, the signature of
a unit OLF switched out of a shared group, or ``bake_saturated_voltage_control``
is set and it sits at its limit to ``_Q_SATURATED_HELD_TOL_MVAR`` (freeze a held
unit at its limit too). Neither applies to an SVC whose own bus still has another
controller inside its range: OLF only clamped it there, the bus still regulating.
Returns the ids of the SVCs frozen: like the generators frozen at a limit, the ones
OLF would switch back to voltage control on a grid asking them for less.
"""
df_bus = _get_buses(network) if df_bus is None else df_bus
svc = network.get_static_var_compensators(
attributes=["regulating", "regulation_mode", "q", "b_min", "b_max", "target_v",
"regulated_element_id", "connected", "bus_id"]
)
if keep_only_main_comp:
svc = _keep_only_main_comp(svc, df_bus)
is_voltage = svc["regulating"] & (svc["regulation_mode"] == "VOLTAGE")
svc = svc[is_voltage]
if not len(svc):
return pd.Index([], dtype=object)
v_kv = df_bus.loc[svc["bus_id"].values, "v_mag"].to_numpy()
# SVC "q" (like generators') is the terminal/receptor-convention result: flip to
# generator/injection convention to compare against the susceptance envelope.
q_gen = -svc["q"].to_numpy()
# an SVC carrying a standby automaton: OLF holds the SVC part, apart from the fixed b0,
# in [b_min, b_max], so its total output ranges over the shifted interval
b0 = _svc_standby_b0(network, svc.index)
qmax = (svc["b_max"].to_numpy() + b0) * v_kv ** 2 # Q[MVAr] = B[S] * V[kV]^2
qmin = (svc["b_min"].to_numpy() + b0) * v_kv ** 2
tol = _q_limit_tol(qmin, qmax)
mask = (q_gen >= qmax - tol) | (q_gen <= qmin + tol)
if mask.any():
reg_bus = _resolve_regulated_bus(network, svc["bus_id"], svc["regulated_element_id"])
held = _target_v_held(network, reg_bus, svc["target_v"], df_bus).to_numpy(bool)
exact = (q_gen >= qmax - _Q_LIMIT_TOL_ABS) | (q_gen <= qmin + _Q_LIMIT_TOL_ABS)
# as for a generator, OLF switches a whole bus: an SVC clamped at its limit while its
# own bus still regulates was only clamped by the split of the bus' reactive power
exact_free = exact & ~_svc_bus_still_regulating(network, svc, exact, _Q_LIMIT_TOL_ABS,
df_bus, keep_only_main_comp)
switched = exact_free & (_n_free_controllers(network, reg_bus, exact, df_bus, keep_only_main_comp) > 0)
if bake_saturated_voltage_control:
# as for a generator: a held SVC is frozen only when saturated, not with headroom left
saturated = ((q_gen >= qmax - _Q_SATURATED_HELD_TOL_MVAR)
| (q_gen <= qmin + _Q_SATURATED_HELD_TOL_MVAR))
saturated &= ~_svc_bus_still_regulating(network, svc, saturated, _Q_SATURATED_HELD_TOL_MVAR,
df_bus, keep_only_main_comp)
mask &= ~held | saturated | switched
else:
mask &= ~held | switched
if mask.any():
upd = pd.DataFrame(index=svc.index[mask])
# unlike Generator.target_q (already generator convention), StaticVarCompensator
# .target_q is receptor convention like its "q" result column -- write the raw
# (unflipped) realized value.
upd["target_q"] = svc["q"].to_numpy()[mask]
upd["regulation_mode"] = "REACTIVE_POWER"
network.update_static_var_compensators(upd)
return pd.Index(svc.index[mask], dtype=object)
def _svc_bus_still_regulating(network, svc, svc_at_limit, tol_mvar, df_bus, keep_only_main_comp=True):
"""Boolean array (aligned on the voltage-mode SVCs ``svc``): another voltage controller of
the SVC's OWN bus -- a regulating generator (after the generator freezes of the bake) or
another of these SVCs -- is not at a limit, to ``tol_mvar`` for a generator and as
``svc_at_limit`` says for an SVC. The SVC counterpart of :func:`_bus_still_regulating`:
OLF switches a bus, not one of its units."""
at_limit = np.asarray(svc_at_limit, dtype=bool)
own_bus = svc["bus_id"].to_numpy()
svc_free = pd.Series((~at_limit).astype(int), index=svc.index)
n_free = svc_free.groupby(own_bus).transform("sum").to_numpy() - svc_free.to_numpy()
gen = network.get_generators(
attributes=["voltage_regulator_on", "q", "min_q", "max_q", "min_q_at_p", "max_q_at_p",
"connected", "bus_id"])
if keep_only_main_comp:
gen = _keep_only_main_comp(gen, df_bus)
gen = gen[gen["voltage_regulator_on"].astype(bool)]
if len(gen):
gq = -gen["q"]
qmin, qmax = _reactive_limits(gen)
gen_free = ~((gq >= qmax - tol_mvar) | (gq <= qmin + tol_mvar))
free_per_bus = gen_free.astype(int).groupby(gen["bus_id"].to_numpy()).sum()
n_free = n_free + free_per_bus.reindex(own_bus).fillna(0).to_numpy(int)
return n_free > 0
def _n_free_controllers(network, svc_reg_bus, svc_exact, df_bus, keep_only_main_comp=True):
"""For each voltage-mode SVC (``svc_reg_bus``: the bus each regulates, ``svc_exact``:
whether it sits exactly at a limit), how many OTHER controllers of that same bus
are still inside their range: the regulating generators not exactly at a Q limit
(after the generator freezes of the bake), and the other SVCs not exactly at a
limit. See :func:`_switched_group_members`, the same test among generators."""
svc_free = pd.Series(~np.asarray(svc_exact, dtype=bool), index=svc_reg_bus.index).astype(int)
n_free = svc_free.groupby(svc_reg_bus.to_numpy()).transform("sum").to_numpy() - svc_free.to_numpy()
gen = network.get_generators(
attributes=["voltage_regulator_on", "q", "min_q", "max_q", "min_q_at_p", "max_q_at_p",
"regulated_element_id", "connected", "bus_id"])
if keep_only_main_comp:
gen = _keep_only_main_comp(gen, df_bus)
gen = gen[gen["voltage_regulator_on"].astype(bool)]
if len(gen):
gq = -gen["q"]
qmin, qmax = _reactive_limits(gen)
gen_free = ~((gq >= qmax - _Q_LIMIT_TOL_ABS) | (gq <= qmin + _Q_LIMIT_TOL_ABS))
gen_reg = _generator_regulated_bus(network, gen)
free_per_bus = gen_free.astype(int).groupby(gen_reg.reindex(gen.index).to_numpy()).sum()
n_free = n_free + free_per_bus.reindex(svc_reg_bus.to_numpy()).fillna(0).to_numpy(int)
return n_free
def _bake_remote_voltage_control(network, keep_only_main_comp=True, df_bus=None):
"""Rewrite *remote* voltage control into *local* control at the solved terminal.
A generator regulating a bus other than its own terminal (``regulated_element_id``
resolving to a different bus -- e.g. holding the 400 kV grid-connection point
across its step-up transformer) is rewritten to regulate its OWN terminal at that
terminal's solved magnitude, and the remote regulation is cleared so the converter
treats it as local control.
At the converged operating point this is exact: the generator's own terminal
already sits at ``v_mag`` with the realized reactive output, so fixing it locally
reproduces the same fixed point (same V everywhere, same Q; the formerly-regulated
remote bus still lands on its solved value). A subsequent loop-free solve -- OLF
(whose loop-free parameters disable remote control anyway) or lightsim2grid --
reproduces the baked state.
Why it exists: lightsim2grid v1 cannot host a remote voltage controller on a slack
bus, and the default distributed slack puts many remote-regulating generators on
slack buses. Making every controller local sidesteps that.
.. warning::
This is a *base-case* faithful approximation. Under a topology change the
generator then holds its own terminal magnitude instead of the remote bus, so
the post-contingency reactive behaviour differs from true remote control.
Operates in place; idempotent (an already-local generator is left untouched).
"""
df_bus = _get_buses(network) if df_bus is None else df_bus
gen = network.get_generators(
attributes=["voltage_regulator_on", "regulated_element_id", "connected", "bus_id"]
)
if keep_only_main_comp:
gen = _keep_only_main_comp(gen, df_bus)
if not len(gen):
return
# "remote" matches the converter's own test (see _aux_add_generators.py): a non-empty
# regulated element that is not the generator's own id.
reg = gen["regulated_element_id"].fillna("")
remote = gen["voltage_regulator_on"] & gen["connected"] & (reg != "") & (reg != gen.index)
gen = gen[remote]
if not len(gen):
return
upd = pd.DataFrame(index=gen.index)
upd["target_v"] = df_bus.loc[gen["bus_id"].values, "v_mag"].values # own terminal, kV
upd["regulated_element_id"] = gen.index # regulate own terminal -> local control
network.update_generators(upd)
def _gen_target_p_range(network, gen):
"""``(min_target_p, max_target_p)`` of each generator of ``gen`` (aligned on it), as
OLF's ``ActivePowerControlHelper`` reads them: the ``activePowerControl`` extension's
bounds where it sets them, ``min_p`` / ``max_p`` otherwise."""
apc = network.get_extensions("activePowerControl")
min_target_p = gen["min_p"].to_numpy(dtype=float, copy=True)
max_target_p = gen["max_p"].to_numpy(dtype=float, copy=True)
if len(apc):
common = gen.index.intersection(apc.index)
if len(common):
pos = gen.index.get_indexer(common)
if "min_target_p" in apc.columns:
v = apc.loc[common, "min_target_p"].to_numpy()
ok = ~np.isnan(v)
min_target_p[pos[ok]] = v[ok]
if "max_target_p" in apc.columns:
v = apc.loc[common, "max_target_p"].to_numpy()
ok = ~np.isnan(v)
max_target_p[pos[ok]] = v[ok]
return min_target_p, max_target_p
def _snap_realized_into_target_range(realized, target_p, min_target_p, max_target_p):
"""The realized dispatch ``realized`` (generator convention) to write as the baked
``target_p``. OLF writes a unit's ``p`` back with a round-off, so a unit dispatched at
one of its limits can come back a hair outside ``[min_target_p, max_target_p]``, even
without any slack share.
``checkActivePowerControl`` then reads that ``target_p`` as outside the limits, and
every later OLF solve of the baked network leaves the unit out of the slack although
the reference solve had it in. A unit whose pre-bake ``target_p`` was inside the range
and whose realized dispatch is outside it by at most ``_ZERO_P_TOL`` is thus put back
on the bound it crossed; anything further off is written as is."""
realized = np.asarray(realized, dtype=float).copy()
target_p = np.asarray(target_p, dtype=float)
inside = (target_p >= min_target_p) & (target_p <= max_target_p)
snap_max = inside & (realized > max_target_p) & (realized <= max_target_p + _ZERO_P_TOL)
snap_min = inside & (realized < min_target_p) & (realized >= min_target_p - _ZERO_P_TOL)
realized[snap_max] = max_target_p[snap_max]
realized[snap_min] = min_target_p[snap_min]
return realized
def _bake_active_power_control_participation(network, gen, bat=None, gen_range=None, bat_apc=None):
"""Zero out active-power (slack-distribution) participation for generators (and
batteries, see below) that PowSyBl OLF's own
``AbstractLfGenerator.checkActivePowerControl`` would exclude:
* dispatched at (approximately) zero MW (``POWER_EPSILON_SI``, regardless of
``min_p`` -- unlike :func:`_bake_generator_not_started`, this check has no
``min_p > 0`` guard);
* an implausible ``max_p`` (``_MAX_PLAUSIBLE_ACTIVE_POWER_MW``, always checked);
* ``target_p`` outside ``[min_target_p, max_target_p]``, or a degenerate
(``max_target_p == min_target_p``) range -- OLF's own defaults have
``useActiveLimits`` on, so these are always checked too. ``min_target_p`` /
``max_target_p`` default to ``min_p`` / ``max_p`` unless the generator's own
``activePowerControl`` extension overrides them, mirroring
``ActivePowerControlHelper``;
* **capped** in the reference distribution: OLF spreads the mismatch by the
sharing key, caps every generator that would cross ``max_target_p`` (for a
positive mismatch; ``min_target_p`` for a negative one) at that limit and
redistributes the rest over the others, so a generator whose realized
dispatch sits at the limit on the side the mismatch pushes it took no share
at all. That capping is a dynamic effect no static weight reproduces; the
sign of the reference mismatch -- the total realized minus dispatched
generation -- is known here, so the generators OLF capped are excluded, and
the static distribution lightsim2grid then derives from the flag is the one
OLF effectively used -- on real grid snapshots the units capped this way
carry a large enough share of the raw key that ignoring them visibly skews
the distribution. This only holds for a mismatch of the same sign as the
reference one -- the common case, a loss increase or a load pick-up -- and
is documented as such in ``_default_distributed_slack``.
``gen`` must be the pre-bake generator frame (``p``, ``target_p``, ``min_p``,
``max_p``), read *before* :func:`_bake_active_power` overwrites ``target_p``
with the realized dispatch -- the discard decision is about what OLF actually
used to build the reference solve, not the post-bake value.
Writes ``participate=False`` into the network's own ``activePowerControl``
extension (created where absent) rather than any lightsim2grid-side state:
lightsim2grid's own ``_default_distributed_slack`` (mirroring the same OLF
rule) already reads exactly this extension's ``participate`` flag when
computing slack weights, so this single write keeps both lightsim2grid and any
subsequent pypowsybl OLF re-solve from putting slack mismatch back onto a
generator OLF itself excluded from participating.
Batteries (``bat``, the same pre-bake frame) follow the same rules -- OLF runs
``checkActivePowerControl`` on them too -- read off their own extension
(:func:`~._aux_battery_apc.battery_active_power_control`), with one more detail of
the capping: a unit is never pushed across 0 MW, so a charging battery is capped at
0 by a positive mismatch (and a discharging one by a negative mismatch). The sign of
the reference mismatch is taken over the generators and the batteries together.
``gen_range`` (the generators' :func:`_gen_target_p_range`) and ``bat_apc`` (the
batteries' :func:`~._aux_battery_apc.battery_active_power_control`) are read off the
network when not given.
Returns ``(pinned_batteries, capped, overshoot)``: the batteries OLF capped that this pypowsybl
cannot mark in their extension (<= 1.16.1 rejects a battery id there) -- the caller
pins their active range on their realized dispatch (``min_p = max_p``), a degenerate
range both OLF and lightsim2grid exclude from the slack -- and the ids of the units
(generators, and batteries marked in their extension) excluded ONLY because OLF capped
them: the ones it would let take a share again of a mismatch of the other sign (see
``bake_outer_loops(..., return_details=True)``). A unit excluded for one of OLF's own
``checkActivePowerControl`` reasons is not in it, nor is a pinned battery (its range
is gone). ``overshoot`` (MW, indexed like ``capped``) is how far beyond its limit each
capped unit was: ``target_p + lambda * weight`` minus that limit (> 0 above an upper
limit, < 0 below a lower one), lambda the common factor of OLF's distribution read off
the units it neither excluded nor capped (0 when there is none).
"""
# not at the top: _aux_battery_apc reads its OLF constants from this module
from ._aux_battery_apc import (
_pypowsybl_exposes_battery_apc,
battery_active_power_control,
olf_participation_weight,
olf_target_p_range,
)
apc = network.get_extensions("activePowerControl")
if gen_range is None:
gen_range = _gen_target_p_range(network, gen)
min_target_p, max_target_p = gen_range
target_p = gen["target_p"].to_numpy()
max_p = gen["max_p"].to_numpy()
zero_target = np.abs(target_p) < _ZERO_P_TOL
maxp_not_plausible = max_p > _MAX_PLAUSIBLE_ACTIVE_POWER_MW
outside_limits = (target_p > max_target_p) | (target_p < min_target_p)
degenerate_range = (max_target_p - min_target_p) < _ZERO_P_TOL
excluded = zero_target | maxp_not_plausible | outside_limits | degenerate_range
# capped in the reference distribution (see the docstring): realized generation
# (result "p" is load convention) at the limit on the side the mismatch pushed.
participate = np.ones(len(gen), bool)
if len(apc) and "participate" in apc.columns:
participate = apc["participate"].reindex(gen.index).fillna(True).to_numpy(bool)
realized = -gen["p"].to_numpy()
solved = np.isfinite(realized)
cand = solved & participate & ~excluded
# the batteries: OLF's rule, read off their own extension, and a range cut at 0 on
# the side opposite their dispatch (OLF keeps the sign of a unit when it caps it)
has_bat = bat is not None and len(bat) > 0
if has_bat:
if bat_apc is None:
bat_apc = battery_active_power_control(network, bat)
b_participate, b_droop, b_min_tp, b_max_tp = bat_apc
b_target_p = bat["target_p"].to_numpy(float)
b_min_p = bat["min_p"].to_numpy(float)
b_max_p = bat["max_p"].to_numpy(float)
b_weight = olf_participation_weight(b_target_p, b_min_p, b_max_p,
b_participate, b_droop, b_min_tp, b_max_tp)
b_min_tp, b_max_tp = olf_target_p_range(b_min_p, b_max_p, b_min_tp, b_max_tp)
b_max_tp = np.where(b_target_p < 0., np.minimum(b_max_tp, 0.), b_max_tp)
b_min_tp = np.where(b_target_p < 0., b_min_tp, np.maximum(b_min_tp, 0.))
b_realized = -bat["p"].to_numpy(float)
b_cand = np.isfinite(b_realized) & (b_weight > 0.)
b_capped = np.zeros(len(bat), dtype=bool)
# the sign of the reference mismatch, over every participant
mismatch = float(np.sum((realized - target_p)[cand]))
if has_bat:
mismatch += float(np.sum((b_realized - b_target_p)[b_cand]))
capped = np.zeros(len(gen), dtype=bool)
if mismatch > _ZERO_P_TOL:
capped = cand & (realized >= max_target_p - _ZERO_P_TOL)
if has_bat:
b_capped = b_cand & (b_realized >= b_max_tp - _ZERO_P_TOL)
elif mismatch < -_ZERO_P_TOL:
capped = cand & (realized <= min_target_p + _ZERO_P_TOL)
if has_bat:
b_capped = b_cand & (b_realized <= b_min_tp + _ZERO_P_TOL)
# How far beyond its limit each capped unit was. OLF shares the slack from the raw
# set-points, p = clamp(target_p + lambda * weight): lambda is read off the units it
# neither excluded nor capped (strictly inside their range), and a capped unit sat at
# target_p + lambda * weight beyond its limit -- the room a later mismatch of the other
# sign has to use up before OLF lets it move (see set_gen_can_participate_slack_overshoot).
gen_w = np.zeros(len(gen))
if len(apc) and "droop" in apc.columns:
droop = apc["droop"].reindex(gen.index).to_numpy(float)
else:
droop = np.full(len(gen), np.nan)
if len(gen):
gen_w = olf_participation_weight(target_p, gen["min_p"].to_numpy(float), max_p, participate,
droop, min_target_p, max_target_p)
free = (cand & ~capped & (gen_w > 0.) & (realized > min_target_p + _ZERO_P_TOL)
& (realized < max_target_p - _ZERO_P_TOL))
lam_samples = [(realized - target_p)[free] / gen_w[free]]
if has_bat:
b_free = (b_cand & ~b_capped & (b_realized > b_min_tp + _ZERO_P_TOL)
& (b_realized < b_max_tp - _ZERO_P_TOL))
lam_samples.append((b_realized - b_target_p)[b_free] / b_weight[b_free])
lam_samples = np.concatenate(lam_samples)
lam = float(np.median(lam_samples)) if lam_samples.size else np.nan
def _overshoot(raw, weight, low, high):
# signed: > 0 above the upper limit, < 0 below the lower one -- for a unit capped at
# 0 MW, the only thing that tells which side of 0 it came from
if not np.isfinite(lam):
return np.zeros(len(raw))
unclamped = raw + lam * weight
beyond = unclamped - high if mismatch > 0. else low - unclamped
beyond = np.maximum(np.where(np.isfinite(beyond), beyond, 0.), 0.)
return beyond if mismatch > 0. else -beyond
excluded |= capped
excluded_ids = gen.index[excluded]
capped_ids = gen.index[capped]
overshoot = pd.Series(_overshoot(target_p, gen_w, min_target_p, max_target_p)[capped],
index=capped_ids, dtype=float)
pinned_batteries = bat.index[b_capped] if has_bat else gen.index[:0]
if has_bat and _pypowsybl_exposes_battery_apc():
# this pypowsybl writes the extension on a battery as on a generator
excluded_ids = excluded_ids.append(pinned_batteries)
capped_ids = capped_ids.append(pinned_batteries)
overshoot = pd.concat([overshoot, pd.Series(
_overshoot(b_target_p, b_weight, b_min_tp, b_max_tp)[b_capped], index=pinned_batteries, dtype=float)])
pinned_batteries = pinned_batteries[:0]
if len(excluded_ids):
already_apc = excluded_ids.intersection(apc.index) if len(apc) else excluded_ids[:0]
new_apc = excluded_ids.difference(already_apc)
if len(already_apc):
network.update_extensions(
"activePowerControl", pd.DataFrame({"participate": False}, index=already_apc)
)
if len(new_apc):
network.create_extensions(
"activePowerControl", pd.DataFrame({"participate": False}, index=new_apc)
)
return pinned_batteries, pd.Index(capped_ids, dtype=object), overshoot
def _bake_active_power(
network,
balance_on_loads,
load_power_factor_constant,
keep_only_main_comp=True,
bake_active_power_control_participation=True,
df_bus=None
):
df_bus = _get_buses(network) if df_bus is None else df_bus
gen = network.get_generators(attributes=["p", "target_p", "min_p", "max_p", "connected", "bus_id"])
if keep_only_main_comp:
gen = _keep_only_main_comp(gen, df_bus)
# the batteries' frame is read before any target_p is overwritten too: they take part
# in the slack (see _bake_active_power_control_participation)
bat = network.get_batteries(attributes=["p", "target_p", "min_p", "max_p", "connected", "bus_id"])
if keep_only_main_comp:
bat = _keep_only_main_comp(bat, df_bus)
# the active target ranges OLF checks, read before the participation bake writes
# into the activePowerControl extension (it only writes `participate` there)
gen_range = _gen_target_p_range(network, gen) if len(gen) else None
bat_apc = None
if len(bat):
# not at the top: _aux_battery_apc reads its OLF constants from this module
from ._aux_battery_apc import battery_active_power_control, olf_target_p_range
bat_apc = battery_active_power_control(network, bat)
pinned_batteries = bat.index[:0]
capped = pd.Index([], dtype=object)
overshoot = pd.Series(dtype=float)
if bake_active_power_control_participation and (len(gen) or len(bat)):
pinned_batteries, capped, overshoot = _bake_active_power_control_participation(
network, gen, bat, gen_range, bat_apc)
if len(gen):
# result p is load convention; target_p is generator convention
gen_target_p = _snap_realized_into_target_range(-gen["p"].to_numpy(), gen["target_p"].to_numpy(),
*gen_range)
network.update_generators(
pd.DataFrame({"target_p": gen_target_p}, index=gen.index)
)
if len(bat):
_, _, b_min_tp, b_max_tp = bat_apc
b_min_tp, b_max_tp = olf_target_p_range(bat["min_p"], bat["max_p"], b_min_tp, b_max_tp)
bat_target_p = pd.Series(
_snap_realized_into_target_range(-bat["p"].to_numpy(), bat["target_p"].to_numpy(),
b_min_tp, b_max_tp),
index=bat.index)
network.update_batteries(
pd.DataFrame({"target_p": bat_target_p}, index=bat.index)
)
if len(pinned_batteries):
# a battery OLF capped, on a pypowsybl that cannot mark its extension: a
# degenerate active range at its realized dispatch takes it out of the slack,
# in OLF (checkActivePowerControl) and in lightsim2grid alike
realized = bat_target_p.loc[pinned_batteries]
network.update_batteries(
pd.DataFrame({"min_p": realized, "max_p": realized}, index=pinned_batteries)
)
if balance_on_loads:
load = network.get_loads(attributes=["p", "q", "connected", "bus_id"])
if keep_only_main_comp:
load = _keep_only_main_comp(load, df_bus)
if len(load):
upd = pd.DataFrame(index=load.index)
upd["p0"] = load["p"] # load convention both sides, no flip
if load_power_factor_constant:
upd["q0"] = load["q"]
network.update_loads(upd)
# the units excluded from the slack only because OLF capped them, and how far beyond
# their limit each was (see the caller)
return capped, overshoot